Sabtu, 06 Juni 2015

Sage 200 Thermal Mass Flow Meter


Specifications

Accuracy: +/– 1% of reading plus 0.5% of full scale
Repeatability: 0.2% of reading
Low End Sensitivity: 5 SFPM (1 SCFM in 6″ pipe)
Response Time: 1 second time constant
Turndown: 100:1
Resolution: 1000:1
Power: 24 +/-10% VDC or 90 – 265 VAC
Output: 4-20 mA
Pulse: 100 mA maximum
Isolated: External powered 4-20 and pulse
Modbus: RS 485 RTU optional
Ratings: Class I, Division 2, NEMA 4, CE
Ambient Temperature: –40 to 150° F (–40 to 65° C)
Type: Insertion probe (1/2″ diameter), flow body (1/4″ to 4″)
Materials: 316 stainless steel and Hastelloy C
Process Temperature Range: –40 to 450°F (–40 to 230° C)

Process Pressure: Max 500 psig


Sage 300 Thermal Mass Flow Meter


Specification :

Accuracy: +/– 1% of reading plus 0.5% of full scale
Repeatability: 0.2% of reading
Low End Sensitivity: 5 SFPM (1 SCFM in 6″ pipe)
Response Time: 1 second time constant
Turndown: 100:1
Resolution: 1000:1
Power: 24 +/-10% VDC or 90 – 265 VAC
Output: 4-20 mA
Pulse: 100 mA maximum
Isolated: External powered 4-20 and pulse
Modbus: RS 485 RTU optional
Ratings: Class I, Division 2, NEMA 4, CE
Ambient Temperature: –40 to 150° F (–40 to 65° C)
Type: Insertion probe (1/2″ diameter), flow body (1/4″ to 4″)
Materials: 316 stainless steel and Hastelloy C
Process Temperature Range: –40 to 450°F (–40 to 230° C)
Process Pressure: Max 500 psig


Integral In-Line Mass Flow Meter


SPECIFICATION :

STYLE  : Integral In-Line Mass Flow Meter
SENSOR: Two reference grade Platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION: <2.5 W
ELECTRONICS: Microprocessor based (Hybrid-Digital)
ELECTRONICS ENCLOSURE: Integral mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes - Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups , C, D T4 (24VDC);
CE (AC Power or 24VDC)
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C), Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC pulse for Totalized value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40° to 150°F (66°C)
FLOW BODY: 316SS Schedule 40 Flow Bodies sized from 1/4" x 6" long to 4" x 12" long.
Male NPT ends standard (Flanges and other options available)
RELAYS: N/A
FLOW CONDITIONING: Flow Conditioners are built in to In-Line Style Flow Bodies from 1/2" to 4"

ENCLOSURE DEPTH: DC: 4.35" ; AC: 5.35"
Share this article :


Integral Insertion Mass Flowmeter


SPESIFICATION :

STYLE : Integral Insertion Mass Flow Meter
SENSOR: Two reference grade platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION: <2.5 W
ELECTRONICS: Microprocessor based (Hybrid-Digital)
ELECTRONICS ENCLOSURE: Integral mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes - Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups B, C, D T4 (24VDC);
CE (AC Power or 24VDC)          
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C),Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC Pulse for Totalized Value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40° to 150°F (66°C)
PROBE STYLE / LENGTH: 1/2" OD Probe (3/4" optional) Lengths 6" to 36"
RELAYS: N/A
FLOW CONDITIONING: Captive Flow Conditioners available upon request with meter purchase
ENCLOSURE DEPTH: DC: 4.35" ; AC: 5.35"


Sage Flowmeter


SPESIFICATION :

STYLE: Remote Insertion Mass Flow Meter
SENSOR: Two reference grade platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION: <2.5 W
ELECTRONICS: Remote-Style Microprocessor based (Hybrid-Digital)
PROBE ENCLOSURE: Junction Box is Explosion Proof, Class I, Div 2, Groups B, C, D (no electronics)
TRANSMITTER ENCLOSURE: Remote mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes - Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups B, C, D T4 (24VDC);
CE (AC Power or 24VDC)
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C), Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC pulse for Totalized value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40°F to 150°F (66°C)
PROBE STYLE / LENGTH: 1/2" OD Probe (3/4" optional) Lengths 6" to 36"
RELAYS: N/A
CABLE LENGTH: 25' Standard (max length 1000')
FLOW CONDITIONING: Captive Flow Conditioners available upon request with meter purchase

TRANSMITTER ENCL DEPTH: DC: 4.35" ; AC: 5.35"


VIDEO

ENTER-TAB1-CONTENT-HERE

RECENT POSTS

ENTER-TAB2-CONTENT-HERE

POPULAR POSTS

ENTER-TAB3-CONTENT-HERE
 

Flowmeter Indonesia | Information for kind of measurement Copyright © 2010 LKart Theme is Designed by Lasantha